Projects:2014S1-29 Measurement and Estimation of Transformer Parameters
Contents
Project Information
The aim of this project is to rigorously combine measurements of practical transformers, with standard transformer-models, using the method of least squares and optimisation techniques, to obtain best estimates of transformer-model parameters. Transformers are the most important building-block of power transmission systems. They are used to transform the magnitudes of voltages and currents. They are used to match sources to loads, to reduce losses, and to improve efficiency. They isolate consumers from dangerous voltages in the transmission network. One of the main problems with modelling transformers is that the fields are distributed in space, which means that lumped models will always be approximate. Also, most practical transformers are significantly non-linear due to saturation of magnetic materials. Transformer models are always provisional, and only apply within certain ranges of current, and frequency. The practical goal of a modeller is to match a chosen equivalent-circuit, to a given device in such a way as to minimise any discrepancy between the observed behaviour of the device and the predicted behaviour of the model.
Outline of Main Tasks
- Task 1: Literature search on transformer models and measurement techniques
- Task 2: Identification of a suitable physical transformer for initial study
- Task 3: Open-circuit tests of the transformer using inductor models
- Task 4: Open-Circuit and Short-circuit tests of the transformer, using inductor, and coupled-magnetic-circuit models.
- Task 5: Full-analysis of the transformer, under many (at least seven...) loading conditions, and full estimates of all parameters.
High Level Design
- Stage 1:
- Basic equipment setup(transformer, current sensor)
- Stage 2:
- SC & OC tests based on the transformer module, transformer parameter estimation
- Stage 3:
- 7 different loading conditions, power source under different frequencies conditions.
Supervisors
- Dr Andrew Allison
- Dr Rastko Zivanovic
Experimentation
Throughout the course of the project three main experiments were conducted. The aim of these experiment sessions was to acquire measurement values for four variables represented in the ideal transformer equivalent: The voltage across the primary terminal, V1, the current flowing through the primary terminal, i1, the voltage across the secondary terminal, V2 and the current flowing through the secondary terminal, i2.
Calibraiton Test
The calibration test was conducted to obtain a relationship between the output voltage signal of the hall-effect current sensors used and the corresponding current flowing through them.
Open Circuit Test
The open circuit test was conducted in order to obtain necessary data to estimate the internal core resistance, Rc, and the magnetizing reactance, Xm of the transformer model.
Short Circuit Test
The short circuit test was conducted in order to obtain necessary data to estimate the total winding resistance R, and the total leakage reactance X of the transformer model.
Workplace
- Bench 6 in Project Lab